CKF - Cooling duct
  CPKF - Duct with the heat pump
  CE - Cooling duct
     

 

CE GOODMAN
CONDENSING AGGREGATES

 


MODEL

CE090-5A

CE120-5A

Cooling power [kW]

25,0

32,0

Power supply

400V/3/50Hz

400V/3/50Hz

Consumption of current [A]

16,8

23,1

Min. oporno¶æ przewodu

20

28

Max. wielko¶æ bezpiecznika [A] (wersja zw³oczna)

30

50

Freon line - vapour

1 3/8"

1 3/8"

Freon line - liquid

5/8"

5/8"

Engine of the fan

249W(2)/ 1,2A(2)

249W(2)/ 1,2A(2)

Capacity of the fan [m3/h]

5330

6320

Dimensions

W width [mm]

1981

1981

D depth [mm]

813

813

H height [mm]

826

826

Weight [kg]

183,0

188,9



BLOWERS OF AIR WITH THE DUCT COOLER

Description:

  • top blowing, possibility of installation in the level,

  • the device to be put only in inner rooms.


MODEL

A90-00-2

A120-00-2

Electric power supply

230V/1/50Hz

230V/1/50Hz

Consumption of current [A]

12,75

19,75

Power of the engine of the fan [kW]

0,75-0,37

0,75-0,37

Min. protection [A]

16,0

20

Freon line - vapour

1 1/8"

2x1 1/8"

Freon line - liquid

3/8"

2x3/8"

Weight [kg]

155,3

165,7


Remark:

The A120 model to be applied with the single CE120 aggregate or two CKF60-61 aggregates.


Table of capacity of air [m3/h]

Model

A90-00-2

A120-00-2

Nominal capacity of air [m3/h]

5100

6800



DUCT BLOWERS WITH THE COOLER
STANDARD VERSION



MODEL

WYMIARY [mm]

A

B

A90-00-2

397

416

A120-00-2

473

373



MINIMAL DIMENSIONS OF BLOWING AND RETURN DUCTS



MODEL

WYMIARY [mm]

BLOWING DUCT

RETURN DUCT

A

B

C

D

A90/120

292

834

572

1182



 Main page | Company information | Heating | Air-conditioning | Ventilation | Contact | Pl | Cz | Ru